Single Action Linear Positioner
Pickup availability could not be loaded
Single-Acting Linear Electropneumatic Positioner — 4-20 mA, IP66, EX ia IIC T4 Ga, Aluminum Body, as it does not require a microprocessor
Cematic's single-acting linear electropneumatic positioner converts the 4-20 mA analog electrical signal from the control system into proportional pneumatic pressure to position single-acting linear actuators. Unlike smart digital positioners, this model operates purely analogically, as it does not incorporate a microprocessor or HART communication.
Its operation is simpler and more direct. The input signal mechanically actuates the pneumatic pilot, therefore it does not require additional electronic processing. The EX ia IIC T4 Ga certification — intrinsically safe — also enables it for installation in classified areas with Group IIC gases, including hydrogen.
Its aluminum body with IP66 protection also guarantees durability in industrial environments with the presence of moisture and vapors.
Electropneumatic vs. smart — when this positioner is the correct specification when HART is not required
The selection between an analog electropneumatic positioner and a smart one depends on the diagnostic, calibration, and cost requirements. The cases where the electropneumatic is the correct specification are described below: The cases where the electropneumatic is the correct specification are described below, as the functionality of the smart positioner is not needed in all projects:
- Processes where remote diagnostics or HART communication are not required — since the electropneumatic positioner covers the basic positioning function: When the process only needs the valve to be positioned proportionally to the 4-20 mA signal, the electropneumatic positioner is sufficient. The smart positioner with HART adds diagnostic functionalities that are not always necessary, therefore increasing the cost without providing a benefit in those cases.
- Projects with budget restrictions where basic functionality is sufficient, since the electropneumatic has a lower cost: The electropneumatic positioner has a lower cost than the smart one, since its analog design is simpler. It is the correct specification when the project budget does not justify the smart positioner and the required function is proportional positioning without remote diagnostics.
- Existing installations where the available signal is only 4-20 mA, given that there is no fieldbus infrastructure: In many industrial installations, the control system only has a 4-20 mA analog signal without IO-Link or HART infrastructure. The electropneumatic positioner is likewise the correct option in those cases as it does not require a bus master or additional configuration.
EX ia — why intrinsically safe is different from EX db enclosure and when it is the correct one
The EX ia IIC T4 Ga certification is a different safety technology from the EX db enclosure of the Ex-Proof smart positioners in the catalog. Both are valid in classified areas, although they apply different safety concepts:
- EX ia — intrinsically safe — since it limits the energy available in the circuit: Intrinsically safe operation works by limiting the electrical energy in the positioner circuit to levels that cannot generate a spark or sufficient heating to ignite the atmosphere. Consequently, no spark is possible, even if the circuit fails. It is the most robust safety concept in Zone 0 and Zone 1 areas.
- Group IIC — suitable for hydrogen and acetylene, since they are the most demanding gases in the classification: Group IIC is the most demanding of the ATEX/IECEx classification. It covers Group IIA and IIB gases and, additionally, hydrogen and acetylene from Group IIC. Therefore, this positioner is the correct specification in processes with hydrogen where Group IIB positioners would be insufficient.
- Temperature class T4 (135°C) — suitable for most industrial gases, although some cryogenic gases require T5: The T4 class guarantees that the surface temperature of the positioner does not exceed 135°C, which covers the auto-ignition temperature of most industrial gases. It is also compatible with the thermal requirements of hydrogen and most hydrocarbons.
Technical specifications that define the application limits of the single-acting linear electropneumatic positioner
| Parameter | Value |
|---|---|
| Positioner type | Analog electropneumatic — without microprocessor |
| Compatibility | Single-acting pneumatic linear actuators |
| Input signal | 4-20 mA |
| Communication | Not applicable — analog positioner |
| Enclosure protection | IP66 |
| Ex certification | EX ia IIC T4 Ga — intrinsically safe |
| Enabled areas | Zone 0, 1 and 2 — Group IIA, IIB and IIC gases and vapors |
| Body material | Aluminum |
| Air connection | 1/4" NPT |
| Pressure gauge connection | 1/8" NPT |
| Calibration | Manual in the field |
Electropneumatic positioner vs. smart positioner — comparison table to select the correct one according to the process
| Criterion | Electropneumatic positioner ← This product | Smart positioner with HART |
|---|---|---|
| Signal type | ✅ 4-20 mA analog — no fieldbus required | 4-20 mA + bidirectional HART |
| Remote diagnostics | ❌ Not available — field inspection only | ✅ HART — position, pressure and alarms from the DCS |
| Calibration | Manual in the field | ✅ Automatic — real-time auto-adjustment |
| Ex certification | ✅ EX ia IIC T4 — intrinsically safe, Group IIC (hydrogen) | EX db IIB T4 — enclosure, Group IIB |
| Enabled Ex areas | ✅ Zone 0, 1 and 2 (including Zone 0) | Zone 1 and 2 |
| Application in processes with H₂ | ✅ Yes — Group IIC covers hydrogen | ❌ No — Group IIB does not cover hydrogen |
| Relative cost | ✅ Lower — for applications without the need for remote diagnostics | Higher — justified when HART and auto-adjustment are required |
Main applications where the single-acting linear electropneumatic positioner is the correct specification
- Globe valve control in flow, pressure or temperature regulation processes: The positioner converts the 4-20 mA signal from the PID controller into the proportional position of the globe valve actuator. It is likewise the correct specification in control loops where continuous positioning without remote diagnostics is required.
Its lower cost compared to the smart positioner makes it suitable for installations with many valves where the budget is a relevant factor.
- Chemical and petrochemical industry with processes handling hydrogen or other Group IIC gases: The EX ia IIC T4 Ga certification is the correct specification in process units with hydrogen, since Group IIB positioners do not cover that gas. The intrinsically safe concept is likewise acceptable in Zone 0 where the EX db enclosure is not enabled.
Applications in energy, water and modernization where the electropneumatic positioner also covers the requirement
- Power generation and steam systems where precise positioning is critical: In power plants, this positioner controls globe valves in steam lines, boiler water and process fluids with a direct 4-20 mA signal from the DCS. Its analog operation without a microprocessor likewise reduces the risk of electronic failure in high-temperature environments.
- Water treatment and dosing systems where the analog signal is the standard: In water treatment plants with control systems that only have a 4-20 mA analog signal, this positioner integrates directly without the need for an additional bus master. It is therefore the simplest and lowest-cost option in those installations.
- Modernization of manual valves to proportional control in installations with an existing 4-20 mA signal: When an installation has available 4-20 mA wiring and needs to convert manual valves to proportional control, this positioner is the lowest-cost and simplest option. Finally, it does not require fieldbus infrastructure or an IO-Link master for its integration.
For the complete range of positioners, see positioner collection →